hey there welcome back to the ask luffy
00:33
podcast
00:35
here we are coming at you again with
00:37
another episode how we doing dan yeah
00:39
we're doing good thanks for coming back
00:41
so we get a question or a request every
00:44
so often for
00:46
energy metering do you guys offer
00:48
something that i can use to
00:51
read consumption yeah measure energy
00:53
consumption yeah a lot of you may not
00:55
even be familiar with it or aware that
00:58
we offer it i mean it's a product we've
00:59
had now for a while um
01:02
last year or more has really taken hold
01:04
we're starting to see a lot of these
01:05
going in but that's our can take a heat
01:07
meter or energy meter the energy meter
01:09
the 7504 series yeah
01:12
so we offer it in
01:15
a variety of sizes and
01:17
configurations yeah a lot a lot of
01:19
options out there with it gives the
01:21
building owner
01:23
of the ability to measure the energy
01:25
being used you know you can measure
01:27
energy for hot water you can measure
01:29
energy for heating
01:31
space heating you know basically it's
01:33
going to be a btu meter
01:35
right it'll measure and record it
01:38
all that information
01:40
you can tap into it remotely if you have
01:43
the data logger yeah we have a data
01:45
logger or user interface that allows you
01:48
to tie into it a user interface will
01:51
convert it from modbus to bacnet so you
01:54
can tie it into a building automation
01:55
system and and watch the usage and be
01:58
able to read and harvest the the
02:01
information off of it exactly nice thing
02:03
about them is
02:05
you know you can tie up to 250 of these
02:08
meters together that's a lot it is it is
02:11
for a large apartment building that
02:13
this is a great option yeah it's perfect
02:16
you know apartment building commercial
02:18
space
02:19
any application where you're going to
02:21
have a common
02:23
utility service
02:25
gas and electric service
02:28
this is going to give you the ability to
02:30
measure
02:31
the amount of btus used in a space so
02:34
you know when you look at calculating
02:35
btus is simple you calculate your delta
02:38
t between supply and return
02:40
times your gallons per minute flow rate
02:42
times 500 for straight water gives you
02:45
the amount of btus used and this
02:47
device will
02:49
come with a supply temperature sensor
02:52
and return temperature sensor and a well
02:54
to install those in
02:56
um and that's how it's going to measure
02:57
that delta t so that's going to give you
02:59
your temperature difference it also
03:01
comes with a flow meter right and we
03:03
have varying sizes here
03:06
being able to
03:07
measure different flow rates essentially
03:10
different cvs so
03:12
a single jet flow meter
03:15
half three quarter in one inch and then
03:17
the multi-jet
03:19
um
03:20
from
03:22
what is it one inch all the way up to
03:24
inch and a half yeah
03:26
yeah and we'll we actually have the unit
03:28
available up to eight inch flanged
03:31
so for large commercial applications we
03:33
have the ability to the sensors are
03:35
going to come factory wired into the
03:37
control
03:38
and that's important
03:40
this control is calibrated and to meet
03:43
the standards it has to have it has to
03:46
be
03:47
tamper proof essentially so it has to
03:49
have those the sensor leads are i
03:51
believe they're 20 foot leads on each
03:53
and they're pre-wired into the control
03:56
and
03:57
they're
03:58
secured in a way that they can't be
04:00
tampered with right and we'll get that
04:02
question on occasion hey can i extend
04:04
the wires you're changing the resistance
04:07
values then which is going to throw that
04:09
off right yeah calibration is going to
04:11
be different right you don't really have
04:12
a way of calibrating it unfortunately no
04:15
that's all done at the factory that's
04:16
all
04:17
and rightfully so right because again
04:20
trying to keep it from being tampered
04:21
with right
04:23
so we had a local project that we had
04:25
these installed in and it was a great
04:27
opportunity it was fun to go out on that
04:29
project yeah you got to go out and see
04:31
it in action and actually help the
04:33
contractor set them up didn't you yeah
04:34
yeah it was fun so it was
04:37
a multi-family project
04:39
it was an existing buildings and there
04:43
were two eight family apartment
04:45
buildings okay that were heated off of
04:48
two boilers the boilers were located in
04:50
the basement of one eight family supply
04:52
and return piping went underground into
04:54
the basement of the second wow
04:56
and then was piped throughout that
04:58
building and they were you know small
05:00
apartments um
05:03
hydronic uh fin tube baseboard for
05:05
heating okay
05:07
but previous to that
05:09
the building owner was paying all
05:11
utilities so he heat was included
05:14
so what that owner had done is he had
05:16
upgraded to high efficient boilers
05:18
he had put an individual electric water
05:20
heater in the basement of each one of
05:22
the apartments so you know now that the
05:25
the electric was separated but the gas
05:27
wasn't okay so
05:29
then in each one of the apartment units
05:32
they installed it can take a heat meter
05:34
okay and it was relatively easy because
05:37
you know being common piping
05:40
and you know
05:41
each
05:42
basement of the
05:44
apartment complex had basements so in
05:47
the basement you know it was common pipe
05:49
throughout the unit and there was a zone
05:51
valve tied to a thermostat for each of
05:53
the apartments sure so after the zone
05:55
valve he installed his supply
05:57
temperature sensor
05:59
on the leaving
06:01
return loop from the apartment going
06:03
back to the main he installed his return
06:05
temperature sensor so that gave him the
06:07
ability to calculate his delta t
06:09
and then on the return side he installed
06:11
the water meter and the water meter
06:13
calculated his flow rates how many
06:15
gallons per minute was flowing through
06:16
that through that loop when it was
06:18
heating and it was interesting because
06:20
you know we were there and
06:22
we were running it and it was
06:24
calculating the delta t it was
06:26
calculating the flow rate you know it
06:27
was anywhere
06:29
you had variable speed pumps on on the
06:31
boilers so it was anywhere from you know
06:34
maybe three quarters to
06:37
one
06:38
and a quarter gallon per minute of flow
06:40
okay through the unit and it was
06:41
measuring the temperature difference and
06:42
it was telling us how many btus that
06:44
unit was using in heating
06:47
very nice
06:48
and then
06:49
they had tied a communication wire from
06:52
each one of they can take us back to the
06:54
boiler room um to one of the data
06:56
loggers okay so
06:58
we were able to go in there you know we
07:00
had to assign each one an address okay
07:03
and again you can put up to 250 cantekas
07:06
on
07:07
a single system sure you only had 16
07:09
there yeah we had 16 other right
07:12
and then at the data logger we were able
07:14
to
07:16
search and found each one of the
07:18
addresses okay and then it was able to
07:20
tell us you know how many btus it was
07:22
using and it's going to record that and
07:24
at the you know end of the month the
07:27
building owner can tie into that he can
07:28
tie a laptop computer into it he didn't
07:30
have a building automation system sure
07:32
but he could go down and plug in with
07:33
his laptop and read all that info right
07:35
pull that information off and and record
07:38
it and and log it well yeah and then it
07:40
gave him the ability to
07:42
look at how many btus they used and
07:45
separate and say okay unit one used you
07:48
know x amount of btus and unit two used
07:50
x amount and then he was able to take
07:53
his gas bill and break that out and bill
07:55
each tenant for the amount of btus they
07:57
use that month sure well that's pretty
07:59
handy to be able to do that yeah it was
08:01
pretty interesting i mean you look at
08:03
going from
08:05
you know having from paying the gas bill
08:08
which
08:09
you know how rentals are you pay the gas
08:11
bill and you drive by and the
08:12
apartment's 80 degrees and the windows
08:14
are open oh yeah i i'm familiar with
08:16
plenty of those situations so now
08:19
when the tenant's paying the utility
08:21
bill
08:21
you're going to see the thermostat set
08:23
lower you're going to see the windows
08:24
close because that you know that's
08:26
affecting them directly it certainly is
08:28
they got to pay for it so
08:30
they're going to
08:31
have a little more care in it yeah and
08:33
the other option he would have had
08:35
would have been to have the municipality
08:38
come out and install a gas meter for
08:39
each unit which is going to be a big
08:41
investment
08:42
and then put a
08:44
boiler in the basement of each of the
08:46
units yeah separating separate boilers
08:49
so that's
08:50
16 boilers 15 boilers that's 16 times
08:53
the maintenance yep
08:55
um yeah it's 16 gas meters gas piping
08:58
throughout the entire building it's a
09:00
huge lake venting would have been next
09:02
to impossible yeah you know because
09:04
either you're going high efficient which
09:06
there you know the
09:07
side-by-side apartments didn't give a
09:08
lot of venting location you know if
09:10
you're mid efficient they didn't have
09:12
chimneys or class b vents to vent them
09:14
so that wouldn't have been a great
09:15
option as well um but this allowed him
09:17
to
09:18
complete his task you know he he
09:21
made the investment in two new boilers
09:24
and he's able to
09:26
allow the tenants now to pay their
09:27
utility bills so
09:29
you know he's recovering recovering that
09:31
as a
09:32
return on investment so to speak yeah
09:34
it's a great option to be able to do
09:35
that
09:36
those jobs are always fun to go to
09:38
weren't they
09:39
the apartments you know to try and
09:41
troubleshoot
09:42
yeah they are because
09:44
you know zone valve is either up in the
09:46
apartment someplace buried under the
09:47
zone
09:48
the baseboard right in the cabinet yeah
09:51
or
09:51
they're in the divided up basement
09:53
somewhere and you don't always have
09:56
access to it right yeah this one was
09:58
really easy this was a like a perfect
10:00
setup for the candeca
10:02
but you could do this in a commercial
10:04
application i mean you you know had they
10:06
had um you know common water heaters and
10:09
they had you know
10:10
supply lines going out to
10:13
you know each of the apartment they
10:14
could have done metering on domestic hot
10:17
water there's four additional inputs
10:18
where they could tie in
10:20
you know for gas usage to help measure
10:22
gas usage or any anything
10:25
you know a
10:26
pulse signal will indicate great
10:30
well i think that pretty well covers it
10:32
doesn't it
10:33
it's uh it's an overview i mean yeah
10:36
it's a general overview of the product
10:38
and as we start getting more questions
10:40
and seeing things we'll be sure to share
10:42
them with you 100 we sure will
10:45
well
10:46
till next time
10:48
thank you for tuning in if you ever need
10:50
help please feel free to contact our
10:52
tech support team anytime at
10:54
techsupport.us
10:57
caleffi.com
10:59
or call us during our business hours at
11:02
7 30 a.m to 4 30 p.m
11:05
central time
11:06
at 414-238-2360